ENG
ENG

GEOTHERM WGB (V) 58,2

Specifications

Specifications Units of phys. qt Standard size
Boiler type 58,2
Heating capacity kW 58200
Water temperature at the exit of the boiler ◦С 150
at the entrance to the boiler 70
EC (efficiency coefficient) of boiler Natural gas % 92,5
diesel 89,7
Fuel consumption Natural gas Nm3/h 6174
diesel kg/h 5357
Exhaust gas temperature Natural gas ◦С 148
diesel 186
Aerodynamic resistance of the boiler (without burner) Pa 2000
Hydraulic resistance MPа 0,2
Design water pressure at the inlet MPа 1,6
Water flow through the boiler t/h 625
Specific emission of nitrogen oxides Natural gas g/m³ 0,08
diesel 0,16
Adjustment range % 30-100
Boiler weight (without burner, without water) kg 65000
Water volume of boiler 8,5
Heating surface area 1823,7

PRODUCT DESCRIPTION

GEOTHERM ® WGB (V) series boilers are designed to produce hot water. Boilers are focused on heat supply of industrial and domestic facilities.

GEOTHERM ® WGB (V) series boilers are manufactured with three temperature schedules 70-95 °C; 70-110 °C; 70-150 °C.

GEOTHERM ® WGB (V) series boilers are produced with a capacity from 35 to 68.9 MW.

The fundamental difference between the boilers of the GEOTHERM ® SPI (M) series from the boilers of the GEOTHERM WB(P); GEOTHERM MEDIA; GEOTHERM WEB(3P) series is that the boiler pipe system has a vertical design. The main advantage of boilers of this series is that at high power boilers take up little space when installed on the foundation. This makes it possible to build high-capacity boilers on relatively small areas.



Main components of GEOTHERM ® WGB (V) series boilers:
  • Collector frame - serves to distribute water flows depending on the hydraulic circuit of the boiler and the connection of the boiler to the external strapping.
  • The convective section is the main part of the boiler pipe system.
  • The support frame serves as the base for the installation of the boiler pipe system.
  • Stiffness belt - serves as a frame to ensure the rigidity of the boiler.
  • The flue duct with an explosive valve - serves as a channel for the discharge of exhaust gases.

GEOTHERM WGB (V) 58.2 vertical type hot water boiler, used in the construction of high-capacity boilers, the advantage of these boilers is that they take up little space when installed on the foundation. The efficiency of the boiler when running on natural gas reaches 92.5%.