ENG
ENG

GEOTHERM WGB (P) 3,15

Specifications





Specifications Units of phys. qt Standard size
Boiler type 3,15
Heating capacity kW 3150
Water temperature at the exit of the boiler ◦С 95 110 150
at the entrance to the boiler 70 70 70
EC (efficiency coefficient) of boiler Natural gas % 93,5
93,8 92,8
diesel 92,1
91,2
90,7
Fuel consumption Natural gas Nm3/h 336
338 338
diesel kg/h 292,7
294,7 295
Exhaust gas temperature Natural gas ◦С 143,5
154 156
diesel 188
196 198
Aerodynamic resistance of the boiler (without burner) Pa 110
112
112
Hydraulic resistance MPа 0,12
0,115
0,13
Design water pressure at the inlet MPа 0,7 
0,9
1,6
Water flow through the boiler t/h 108,3
67,7 33,8
Specific emission of nitrogen oxides Natural gas g/m³ 0,08
0,08 0,08
diesel 0,16
0,16 0,16
Adjustment range % 30-100
30-100
30-100
Boiler weight (without burner, without water) kg 5170 
6200
6000
Water volume of boiler 1
1,1
1,1
Heating surface area 134,2
140
140

PRODUCT DESCRIPTION

GEOTHERM ® WGB (P) series boilers are designed to produce hot water. Boilers are focused on heat supply of industrial and domestic facilities.

GEOTHERM ® WGB (P) series boilers are manufactured with three temperature schedules 70-95 °C; 70-110 °C; 70-150 °C.

Boilers of the GEOTHERM ® VWS (P) series are produced with a capacity from 0.63 to 58.2 MW.

The fundamental difference between the boilers of the GEOTHERM ® WB (P) series from the boilers of the GEOTHERM WEB(3P); GEOTHERM WEB; GEOTHERM WEB(V) series is that the exhaust gases after burning the torch of the burner immediately pass through the convective surface.





Main components of GEOTHERM ® WGB (P) series boilers:

  • Collector frame - serves for the distribution of water flows depending on the hydraulic circuit of the boiler and the connection of the boiler to the external strapping.

  • The convective section is the main part of the boiler pipe system.

  • The support frame serves as the base for the installation of the boiler pipe system.

  • Stiffness belt - serves as a frame to ensure the rigidity of the boiler.

  • The flue duct with an explosive valve - serves as a channel for the discharge of exhaust gases. 

Unlike the previous model, this boiler operates in three temperature schedules. The temperature at the outlet of the boiler reaches 150 ° C.